WELD-KA SOLVENT CEMENTS MUST NEVER BE USED IN A PVC OR CPVC SYSTEM USING OR BEING TESTED BY COMPRESSED AIR OR GASES.

Average Initial Set Schedule For WELD.KA PVC / CPVC Solvent Cements

Temperature Range

Pipe Sizes
1/2" to 11/4"

Pipe Sizes
11/2" to 2"

Pipe Sizes
21/2" to 8"

Pipe Sizes
10" to 15"

Pipe Sizes
15"+

20° to 50°C

2 min

5 min

30 min

2 hrs

4 hrs

5° to 20°C

5 min

10 min

2 hrs

8 hrs

16 hrs

-10° to 15°C

10 min

15 min

12 hrs

24 hrs

48 hrs

Note - Initial set schedule is the necessary time to allow before the joint can be carefully handled. In damp or humid weather allow 50% more set time.


AVERAGE JOINT CURE SCHEDULE
FOR WELD-KA PVC/CPVC SOLVENT CEMENTS*

Relative Humidity 60% or Less

Cure Time
Pipe Sizes
1/2" to 11/4"

Cure Time
Pipe Sizes
11/2" to 2"

Cure Time
Pipe Sizes
21/2" to 8"

Cure Time Pipe Sizes 10" to 15"

Cure Time Pipe Sizes 15"+

Temperature Range During Assembly and Cure Periods

up to
160 psi

160-370 psi

up to
160 psi

160-315 psi

up to
160 psi

160-315 psi

up to 100 psi

up to 100 psi

20° to 50°C

15 min

6 hrs

30 min

12 hrs

11/2 hrs

24 hrs

48 hrs

72 hrs

5° to 20°C

20 min

12 hrs

45 min

24 hrs

4 hrs

48 hrs

96 hrs

6 days

-10° to 15°C

30 min

48 hrs

1 hr

96 hrs

72 hrs

8 days

8 days

14 days

Note - Joint cure schedule is the necessary time to allow before pressurizing system. In damp or humid weather allow 50% more cure time.
**These figures are estimates based on our laboratory tests; extended set and cure times are required for chemical applications.
Due to the many variables in the field, these figures should be used as a general guide only.


 
 
 
Copyright © 2008 3P International
Home | Products | MSDS | FAQ | Contact
All rights reserved. About | How to Guide | Selection Guide | Set & Cure Time
Hot & Cold Weather | Application & Accessories | Order From | Client Lit